Hi,
My eBUS scan detects a Vaillant device on address 15 that has no matching config file:
[main error] unable to load scan config 15: no file from vaillant with prefix 15 matches ID "b7s00", SW0422, HW5503
[main error] scan config 15: ERR: element not found
Scan output:
scan.15 = ;Vaillant;B7S00;0422;5503
scan.15 id = 21;17;22;0020197167;0082;005354;N7
Setup:
- ebusd 26.1.26.1
- eBUS Adapter Shield C6 (Stick edition), USB enhanced mode
- Boiler side (address 08) scans fine as BAI00, loads vaillant/08.bai.csv without issue
This device is likely my MiPro room thermostat. Is there an existing config close to this ID/SW/HW range I could test, or would this need a new file? Happy to test and report back if there's a candidate config or if you need more scan data.
Thanks!
root@Tower:~# docker exec -it ebusd ebusctl find -a
bai AccessoriesOne = no data stored
bai AccessoriesTwo = no data stored
bai AntiCondensValue = no data stored
bai BlockTimeHcMax = no data stored
bai BoilerType = no data stored
bai ChangesDSN = no data stored
bai CounterStartAttempts3 = no data stored
bai CounterStartAttempts4 = no data stored
bai Currenterror = no data stored
bai DateTime = no data stored
bai DCFTimeDate = no data stored
bai DeactivationsTemplimiter = no data stored
bai DeltaFlowReturnMax = no data stored
bai DisplayMode = no data stored
bai DSN = no data stored
bai DSNStart = no data stored
bai EBusHeatcontrol = no data stored
bai EbusSourceOn = no data stored
bai EbusVoltage = no data stored
bai Errorhistory = no data stored
bai Expertlevel_ReturnTemp = no data stored
bai ExternalFaultmessage = no data stored
bai ExternalFlowTempDesired = no data stored
bai ExternalHwcSwitch = no data stored
bai ExternGasvalve = no data stored
bai ExtFlowTempDesiredMin = no data stored
bai ExtStorageModulCon = no data stored
bai FanHours = no data stored
bai FanMaxSpeedOperation = no data stored
bai FanMinSpeedOperation = no data stored
bai FanPWMSum = no data stored
bai FanPWMTest = no data stored
bai FanSpeed = no data stored
bai FanStarts = no data stored
bai Flame = no data stored
bai FlameSensingASIC = no data stored
bai FloorHeatingContact = no data stored
bai FlowsetHcMax = no data stored
bai FlowSetPotmeter = no data stored
bai FlowSetPotmeter = no data stored
bai FlowTemp = no data stored
bai FlowTempDesired = no data stored
bai FlowTempMax = no data stored
bai Fluegasvalve = no data stored
bai FluegasvalveOpen = no data stored
bai Gasvalve3UC = no data stored
bai GasvalveASICFeedback = no data stored
bai GasvalveUC = no data stored
bai GasvalveUCFeedback = no data stored
bai HcPumpMode = no data stored
bai HcPumpStarts = no data stored
bai HcUnderHundredStarts = no data stored
bai HeatingSwitch = no data stored
bai HeatingSwitch = no data stored
bai HwcImpellorSwitch = no data stored
bai HwcSetPotmeter = no data stored
bai HwcSetPotmeter = no data stored
bai HwcSwitch = no data stored
bai HwcSwitch = no data stored
bai HwcTemp = no data stored
bai HwcTempDesired = no data stored
bai HwcTempMax = no data stored
bai HwcTypes = no data stored
bai HwcUnderHundredStarts = no data stored
bai HwcWaterflowMax = no data stored
bai Ignitor = no data stored
bai InitialisationEEPROM = no data stored
bai Maintenancedata_HwcTempMax = no data stored
bai MinIgnitiontime = no data stored
bai ModulationDesired = no data stored
bai NightTimeOffset = no data stored
bai OverflowCounter = no data stored
bai ParamToken = no data stored
bai PartloadHcKW = no data stored
bai PartnumberBox = no data stored
bai PositionValveSet = no data stored
bai PowerValue = no data stored
bai PrAPSCounter = no data stored
bai PrAPSSum = no data stored
bai PrEnergyCountHc1 = no data stored
bai PrEnergyCountHc2 = no data stored
bai PrEnergyCountHc3 = no data stored
bai PrEnergyCountHwc1 = no data stored
bai PrEnergyCountHwc2 = no data stored
bai PrEnergyCountHwc3 = no data stored
bai PrEnergySumHc1 = no data stored
bai PrEnergySumHc2 = no data stored
bai PrEnergySumHc3 = no data stored
bai PrEnergySumHwc1 = no data stored
bai PrEnergySumHwc2 = no data stored
bai PrEnergySumHwc3 = no data stored
bai ProductionByte = no data stored
bai PrVortexFlowSensorValue = no data stored
bai PumpHours = no data stored
bai PumpHwcFlowNumber = no data stored
bai PumpHwcFlowSum = no data stored
bai PumpPower = no data stored
bai PumpPowerDesired = no data stored
bai RemainingBoilerblocktime = no data stored
bai ReturnTemp = no data stored
bai ReturnTempMax = no data stored
bai SetMode = auto;0.0;50.0;-;1;0;0;0;0;0
bai SHEMaxDeltaHwcFlow = no data stored
bai SHEMaxFlowTemp = no data stored
bai SolBackTemp = no data stored
bai Statenumber = no data stored
bai Status01 = 42.0;39.5;-;35.0;46.0;off
bai Status02 = off;20;80.0;90;60.0
bai Status16 = no data stored
bai Status = no data stored
bai StatusCirPump = on
bai StorageLoadPumpHours = no data stored
bai StorageloadPumpStarts = no data stored
bai StorageTemp = no data stored
bai StorageTempMax = no data stored
bai TargetFanSpeedOutput = no data stored
bai TempDiffBlock = no data stored
bai TempDiffFailure = no data stored
bai TempGradientFailure = no data stored
bai Templimiter = no data stored
bai TemplimiterFault = no data stored
bai TemplimiterWithNTC = no data stored
bai TempMaxDiffExtTFT = no data stored
bai Testbyte = no data stored
bai TimerInputHc = no data stored
bai ValveStarts = no data stored
bai VolatileLockout = no data stored
bai VolatileLockoutIFCGV = no data stored
bai VortexFlowSensor = no data stored
bai WarmstartDemand = no data stored
bai WaterHcFlowMax = no data stored
bai WaterPressure = no data stored
bai WaterpressureBranchControlOff = no data stored
bai WaterpressureMeasureCounter = no data stored
bai WaterpressureVariantSum = no data stored
bai WPPostrunTime = no data stored
bai WPSecondStage = no data stored
Broadcast Datetime = no data stored
Broadcast Error = no data stored
Broadcast HwcStatus = no data stored
Broadcast Id = no data stored
Broadcast IdAnswer = no data stored
Broadcast IdQuery = no data stored
Broadcast Load = no data stored
Broadcast Outsidetemp = 20.141
Broadcast Queryexistence = (empty for 31fe07fe00 / )
Broadcast Signoflife = no data stored
Broadcast Vdatetime = 21:49:02;31.08.2026
Broadcast Vdatetime = no data stored
General Valuerange = no data stored
Memory Eeprom = no data stored
Memory Ram = no data stored
Scan Id = no data stored
scan.08 = Vaillant;BAI00;0609;3302
Scan.08 Id = 21;17;25;0010017345;1610;008262;N5
scan.15 = Vaillant;B7S00;0422;5503
Scan.15 Id = 21;17;22;0020197167;0082;005354;N7
Hi,
My eBUS scan detects a Vaillant device on address 15 that has no matching config file:
[main error] unable to load scan config 15: no file from vaillant with prefix 15 matches ID "b7s00", SW0422, HW5503
[main error] scan config 15: ERR: element not found
Scan output:
scan.15 = ;Vaillant;B7S00;0422;5503
scan.15 id = 21;17;22;0020197167;0082;005354;N7
Setup:
This device is likely my MiPro room thermostat. Is there an existing config close to this ID/SW/HW range I could test, or would this need a new file? Happy to test and report back if there's a candidate config or if you need more scan data.
Thanks!
root@Tower:~# docker exec -it ebusd ebusctl find -a
bai AccessoriesOne = no data stored
bai AccessoriesTwo = no data stored
bai AntiCondensValue = no data stored
bai BlockTimeHcMax = no data stored
bai BoilerType = no data stored
bai ChangesDSN = no data stored
bai CounterStartAttempts3 = no data stored
bai CounterStartAttempts4 = no data stored
bai Currenterror = no data stored
bai DateTime = no data stored
bai DCFTimeDate = no data stored
bai DeactivationsTemplimiter = no data stored
bai DeltaFlowReturnMax = no data stored
bai DisplayMode = no data stored
bai DSN = no data stored
bai DSNStart = no data stored
bai EBusHeatcontrol = no data stored
bai EbusSourceOn = no data stored
bai EbusVoltage = no data stored
bai Errorhistory = no data stored
bai Expertlevel_ReturnTemp = no data stored
bai ExternalFaultmessage = no data stored
bai ExternalFlowTempDesired = no data stored
bai ExternalHwcSwitch = no data stored
bai ExternGasvalve = no data stored
bai ExtFlowTempDesiredMin = no data stored
bai ExtStorageModulCon = no data stored
bai FanHours = no data stored
bai FanMaxSpeedOperation = no data stored
bai FanMinSpeedOperation = no data stored
bai FanPWMSum = no data stored
bai FanPWMTest = no data stored
bai FanSpeed = no data stored
bai FanStarts = no data stored
bai Flame = no data stored
bai FlameSensingASIC = no data stored
bai FloorHeatingContact = no data stored
bai FlowsetHcMax = no data stored
bai FlowSetPotmeter = no data stored
bai FlowSetPotmeter = no data stored
bai FlowTemp = no data stored
bai FlowTempDesired = no data stored
bai FlowTempMax = no data stored
bai Fluegasvalve = no data stored
bai FluegasvalveOpen = no data stored
bai Gasvalve3UC = no data stored
bai GasvalveASICFeedback = no data stored
bai GasvalveUC = no data stored
bai GasvalveUCFeedback = no data stored
bai HcPumpMode = no data stored
bai HcPumpStarts = no data stored
bai HcUnderHundredStarts = no data stored
bai HeatingSwitch = no data stored
bai HeatingSwitch = no data stored
bai HwcImpellorSwitch = no data stored
bai HwcSetPotmeter = no data stored
bai HwcSetPotmeter = no data stored
bai HwcSwitch = no data stored
bai HwcSwitch = no data stored
bai HwcTemp = no data stored
bai HwcTempDesired = no data stored
bai HwcTempMax = no data stored
bai HwcTypes = no data stored
bai HwcUnderHundredStarts = no data stored
bai HwcWaterflowMax = no data stored
bai Ignitor = no data stored
bai InitialisationEEPROM = no data stored
bai Maintenancedata_HwcTempMax = no data stored
bai MinIgnitiontime = no data stored
bai ModulationDesired = no data stored
bai NightTimeOffset = no data stored
bai OverflowCounter = no data stored
bai ParamToken = no data stored
bai PartloadHcKW = no data stored
bai PartnumberBox = no data stored
bai PositionValveSet = no data stored
bai PowerValue = no data stored
bai PrAPSCounter = no data stored
bai PrAPSSum = no data stored
bai PrEnergyCountHc1 = no data stored
bai PrEnergyCountHc2 = no data stored
bai PrEnergyCountHc3 = no data stored
bai PrEnergyCountHwc1 = no data stored
bai PrEnergyCountHwc2 = no data stored
bai PrEnergyCountHwc3 = no data stored
bai PrEnergySumHc1 = no data stored
bai PrEnergySumHc2 = no data stored
bai PrEnergySumHc3 = no data stored
bai PrEnergySumHwc1 = no data stored
bai PrEnergySumHwc2 = no data stored
bai PrEnergySumHwc3 = no data stored
bai ProductionByte = no data stored
bai PrVortexFlowSensorValue = no data stored
bai PumpHours = no data stored
bai PumpHwcFlowNumber = no data stored
bai PumpHwcFlowSum = no data stored
bai PumpPower = no data stored
bai PumpPowerDesired = no data stored
bai RemainingBoilerblocktime = no data stored
bai ReturnTemp = no data stored
bai ReturnTempMax = no data stored
bai SetMode = auto;0.0;50.0;-;1;0;0;0;0;0
bai SHEMaxDeltaHwcFlow = no data stored
bai SHEMaxFlowTemp = no data stored
bai SolBackTemp = no data stored
bai Statenumber = no data stored
bai Status01 = 42.0;39.5;-;35.0;46.0;off
bai Status02 = off;20;80.0;90;60.0
bai Status16 = no data stored
bai Status = no data stored
bai StatusCirPump = on
bai StorageLoadPumpHours = no data stored
bai StorageloadPumpStarts = no data stored
bai StorageTemp = no data stored
bai StorageTempMax = no data stored
bai TargetFanSpeedOutput = no data stored
bai TempDiffBlock = no data stored
bai TempDiffFailure = no data stored
bai TempGradientFailure = no data stored
bai Templimiter = no data stored
bai TemplimiterFault = no data stored
bai TemplimiterWithNTC = no data stored
bai TempMaxDiffExtTFT = no data stored
bai Testbyte = no data stored
bai TimerInputHc = no data stored
bai ValveStarts = no data stored
bai VolatileLockout = no data stored
bai VolatileLockoutIFCGV = no data stored
bai VortexFlowSensor = no data stored
bai WarmstartDemand = no data stored
bai WaterHcFlowMax = no data stored
bai WaterPressure = no data stored
bai WaterpressureBranchControlOff = no data stored
bai WaterpressureMeasureCounter = no data stored
bai WaterpressureVariantSum = no data stored
bai WPPostrunTime = no data stored
bai WPSecondStage = no data stored
Broadcast Datetime = no data stored
Broadcast Error = no data stored
Broadcast HwcStatus = no data stored
Broadcast Id = no data stored
Broadcast IdAnswer = no data stored
Broadcast IdQuery = no data stored
Broadcast Load = no data stored
Broadcast Outsidetemp = 20.141
Broadcast Queryexistence = (empty for 31fe07fe00 / )
Broadcast Signoflife = no data stored
Broadcast Vdatetime = 21:49:02;31.08.2026
Broadcast Vdatetime = no data stored
General Valuerange = no data stored
Memory Eeprom = no data stored
Memory Ram = no data stored
Scan Id = no data stored
scan.08 = Vaillant;BAI00;0609;3302
Scan.08 Id = 21;17;25;0010017345;1610;008262;N5
scan.15 = Vaillant;B7S00;0422;5503
Scan.15 Id = 21;17;22;0020197167;0082;005354;N7